Support request: Ever (Phoenixtec) PowerLine RT Pro 3000 SNMP sysOID .1.3.6.1.4.1.935.10.1 #3088
Description
Device information
- Vendor/Brand: Ever (Phoenixtec)
- Model: PowerLine RT Pro 3000
- Interface: NMC (SNMP v3)
- NMC firmware version: [please fill in from web GUI]
- sysOID:
.1.3.6.1.4.1.935.10.1
NUT information
- NUT version: 2.8.0
- Driver: snmp-ups
- OS/Distribution: Debian 12
Problem description
When starting the snmp-ups driver, the following message is displayed:
No matching MIB found for sysOID '.1.3.6.1.4.1.935.10.1'!
Please report it to NUT developers, with an 'upsc' output for your device.
Going back to the classic MIB detection method.
Despite this, the UPS works with mibs = auto or mibs = ietf.
Instant commands supported are limited (load.off/on, beeper control, battery tests), but there is no per-outlet control.
ups.conf:
[ups01-snmp]
driver = snmp-ups
port = 192.168.1.244
# SNMPv3
snmp_version = v3
secLevel = authPriv
secName = xxx
authProtocol = MD5
authPassword = xxxx
privProtocol = DES
privPassword = xxxxx
mibs = auto
pollfreq = 5
desc = "Ever PowerLine RT Pro 3k + NMC (SNMPv3)"
Full upsc output
upsc ups01-snmp@localhost:
Init SSL without certificate database
battery.charge: 100
battery.current: -0.10
battery.runtime: 59940
battery.runtime.low: 0
battery.temperature: 20
battery.voltage: 80.10
device.contact: Technical Support Center
device.description: Network Management Card for UPS
device.location: B1-S1-SS2
device.mfr: EPPC
device.model: ON-LINE
device.type: ups
driver.name: snmp-ups
driver.parameter.authProtocol: MD5
driver.parameter.mibs: auto
driver.parameter.pollfreq: 5
driver.parameter.pollinterval: 2
driver.parameter.port: 192.168.1.244
driver.parameter.privProtocol: DES
driver.parameter.secLevel: authPriv
driver.parameter.snmp_version: v3
driver.parameter.synchronous: auto
driver.version: 2.8.0
driver.version.data: tripplite MIB 1.54
driver.version.internal: 1.21
input.bypass.frequency: -0.10
input.bypass.phases: -1
input.current: -0.10
input.frequency: 50
input.frequency.nominal: 50
input.phases: 1
input.realpower: -1
input.transfer.high: 0
input.transfer.low: 0
input.voltage: 236
input.voltage.nominal: 230
output.current: 0
output.frequency: 50
output.frequency.nominal: -0.10
output.phases: 1
output.power.nominal: -1
output.realpower: 0
output.realpower.nominal: -1
output.voltage: 230
output.voltage.nominal: -1
ups.beeper.status: disabled
ups.firmware: 02.14
ups.firmware.aux: 3.6.0.1
ups.load: 0
ups.mfr: EPPC
ups.model: ON-LINE
ups.status: OL
ups.test.result: done and passed
ups.timer.shutdown: -1
ups.timer.start: -1
Steps to reproduce
- Configure
ups.confwith:[tups01-snmp] driver = snmp-ups port = 192.168.x.x snmp_version = v3 secLevel = authPriv secName = zbxups authProtocol = MD5 authPassword = **** privProtocol = DES privPassword = **** mibs = auto
Run upsdrvctl start.
See the sysOID detection warning in logs.
Requested:
Add recognition of sysOID .1.3.6.1.4.1.935.10.1 (Ever / Phoenixtec PowerLine RT Pro 3000) to snmp-ups.
Confirm whether vendor-specific outlet control is available through this NMC.
Additional notes
There are two identical units with the same sysOID and behavior.
SNMPv3 authPriv (MD5/DES) is required by the environment.
If needed I can provide full SNMP walk of .1.3.6.1.2.1.33 and .1.3.6.1.4.1.935 branches.
Thank you!
Metadata
Metadata
Assignees
Labels
Type
Projects
- StatusShow more project fieldsTodo
Activity
jimklimov commentedon Sep 12, 2025
Hello, please note that like much other FOSS, this is a volunteer-supported open source project, done in spare time for fun or to scratch one's own itch. Personally, I can't commit to making the requested changes, but can offer some pointers how you or someone else could do them (SNMP walks would be helpful in either case):
drivers/*-mib.c) for examples that havesomething.%i.somethingin the NUT datapoint names, where the%iis automatically substituted for numbered outlet, sensor, etc. number.azael-azael commentedon Sep 13, 2025
Thank you for answer.
Additional informations:
On mibs=auto I repeatedly get:
No matching MIB found for sysOID '.1.3.6.1.4.1.935.10.1'! Going back to the classic MIB detection method.
Detected ON-LINE on host 192.168.1.244 (mib: tripplite 1.54)
[tups06-snmp] unhandled ASN 0x81 received from 1.3.6.1.2.1.33....
[tups06-snmp] unhandled ASN 0x80 received from 1.3.6.1.2.1.33....
With mibs=ietf the device works; the “unhandled ASN …” lines still appear for non-implemented optional UPS-MIB entries, but functionality is OK.
SNMP proof (vendor EPPC-MIB)
sysDescr / sysObjectID:
1.3.6.1.2.1.1.1.0 = "Network Management Card for UPS"
1.3.6.1.2.1.1.2.0 = .1.3.6.1.4.1.935.10.1
Segment 1 state (works) and Segment 2 (not supported on this unit):
.1.3.6.1.4.1.935.10.1.1.5.5.0 = 2 # upsELoadSegment1State = on(2)
.1.3.6.1.4.1.935.10.1.1.5.10.0 = 5 # upsELoadSegment2State = not-support(5)
Segment 1 control (used successfully in production):
OFF now: .1.3.6.1.4.1.935.10.1.1.5.1.0 i 0 (upsELoadSegment1OffDelay = 0)
ON now: .1.3.6.1.4.1.935.10.1.1.5.2.0 i 0 (upsELoadSegment1OnDelay = 0)
Semantics: INTEGER -1..32767 (0=immediate, -1=cancel, >0 seconds)